EPM-S405 with wire break monitoring switched off

Description of the behavior:

A plausible value is displayed for an unconnected input (e.g. between 40°C and 70°C).

 

Conditions under which the behavior occurs:

  • On the EPM-S405 IO module, the open-circuit monitoring has been switched off
  • One or more inputs of the module are not connected (Unconnected). 

 
Affected products:

EPM-S405 (resistor module of the I/O System 1000)


Short-term measures, Recommendations, Rating:
When using the EPM-S405 with open inputs, open-circuit monitoring should always be activated so that the value 32767 can be used for recognition.
This behavior is not a failure. A change is not planned.

[Automatic Translation]