2-pole mains supply for 400 V inverter

Application:

Mains supply of 400 V-inverters with any 2-pole mains voltage without restriction of the usable motor power

Description:

In the mains supply the following additional components are required:
1. Isolation transformer: Prim. 1x 230 V or current voltage, Sek.2 x 230 V with centre tap (power see table below)
2. Protection varistor, rated voltage 510 V, at least 2 W (e. g. SIOV S20k510)
3. Bridge rectifier, rated voltage at least 1.600 V (rated current see table)
4. According to the device power between 2x one and 2x three (in a row) NTC-resistors (data and quantity see table)
5. 2 x DC-bus capacitors, rated voltage 400 V DC (capacity see table)

Prated Motor  Prated Transformer Irated rectifier(min) NTC-restistors R/I     DC-bus capacitor

1.5 kW         4.0 kVA              16 A              2 x 20 Ohm / 8 A            2 x 1.1 mF

2.2 kW         5.0 kVA              20 A              2 x 10 Ohm / 15 A           2 x 1.5 mF

3.0 kW         7.5 kVA              25 A              2 x 10 Ohm / 15 A           2 x 2.2 mF

4.0 kW        10.0 kVA              35 A              2 x 5.0 Ohm / 20 A          2 x 3.3 mF

5.5 kW        12.5 kVA              50 A              4 x 2.0 Ohm / 25 A          2 x 3.6 mF

7.5 kW        15.0 kVA              50 A              6 x 1.0 Ohm / 30 A          2 x 4.4 mF

11.0 kW       20.0 kVA              75 A              4 x 1.0 Ohm / 40 A          2 x 6.6 mF

The additional components has to be connected according to the following diagram: