Which products are affected?
Engineer HighLevel V2.5
Engineer StateLevel V2.5
What happens?
The oscillogram is indicated with a wrong scaling on the time axis.
When does the problem occur?
The response described above occurs if 200 µs is selected as time basis.
Possible diagnostics?
None.
Short-term measures/recommendations?
- Select another time basis than 200 µs.
- Install Service Pack 3 for Engineer V2.5. Once the Service Pack has been installed 200 µs can no longer be selected as time basis.
Note: It may happen that the time basis 20 ms can be selected twice. Both entries can be selected.
Evaluation:
The oscillogram is not displayed correctly. Thanks to Service Pack 3 for Engineer V2.5 this function restriction has been eliminated.