Project without cam profile functionality is not accepted by the 9400 (elimination)

Which products are affected?
Engineer HighLine V2.5

What happens?
If an Engineer project has been downloaded the 9400 drive refuses to accept the application which can therefore not be started.

When does the problem occur?
The response described before occurs if an application without cam profile functionality is loaded to a 9400 drive in which an application with cam profile functionality is already existent.

Possible diagnostics?
None.

Short-term measures/recommendations?
Install Service Pack 3 for Engineer V2.5. Once this installation has been executed the Engineer can be used to load a project without cam profile functionality to the 9400 drive irrespective of the type of project which has been in the drive controller before.

Evaluation:
The function restriction occurs if a project without cam profile functionality is loaded to a 9400 drive in which an application with cam profile functionality is already existent.
Thanks to Service Pack 3 for Engineer V2.5 this function restriction has been eliminated.