Corrected from:EASY Starter V1.13
Response of the new version:
The function restriction has been solved. If the load moment of inertia is unknown at the time of selection of the motor, it is assumed to be 0 for the calculations taking place.
What happens?
Selecting a motor via the <Select Motor > button (motor from catalogue) on the 'Settings' tab, is terminated with the following message:
Parameter setting ended with errors
0x2910:002 Inertia settings: Load inertia ? kg cm2
Error while reading parameter: Value is not initialized.
When does this behaviour occur?
The above-described behaviour occurs when adding an i550 frequency inverter 'offline from package' in the EASY Starter and selecting and inserting a motor via the motor catalogue ('Settings' tab, <Select Motor> button).
Which products are affected?
EASY Starter from V1.12
Short-term measures:
Open the parameter list and enter the correct load moment of inertia for the parameter 0x2910:002. After this, use the <Select Motor> button and add the motor once again to the parameter set.
Evaluation/recommendations:
After adding the i550 frequency inverter via the 'Offline from Package' tab, the parameter 0x2910:002 is not initialised with a value. Therefore, parameter setting is aborted with errors when a motor is selected.