i950 TAs: Quickstop Application with Target Velocity(0x60FF) parameter (corrected from V01.03.07)

Corrected from:
i950 Servo inverters FW:  from  V01.03.07.xx

Response of the new version: 
The Quickstop Application function delays the drive to a standstill as expected.
(The Target Velocity parameter (0x60FF) is not used by the application and is set cyclically to 0).

 
What happens?
If a value unequal 0 is parameterized in the Target Velocity parameter (0x60FF), when the Quickstop Application function is activated, the drive does not decelerate to standstill as expected but to the speed set in 0x60FF.
 
When does the behaviour occur?
In the Target Velocity parameter (0x60FF), a value unequal to 0 is parameterized.
 
Which products are affected?
i950 servo inverter with technology application (TA)

Short-term measures:
Check parameter 0x60FF, and parameterize the value 0 if necessary.  
This parameter is not used in the TAs.