i950 All TAs : Monitoring signal / No more values after switching (corrected as of V1.5.2)
Corrected from:
Servo inverter i950 FW V01.05.02.1788 (Update via EASY Package Manager)
Response of the new version:
Via the parameter "Display Signal 1"/"DisplaySignal 2", the correct signal is output at any time, regardless of how often it is switched over
What happens?
Only the value 0 is output via the "Display signal 1"/"Display signal 2" parameter.
When does the behaviour occur?
The selection parameter "Source display signal 1"/"Source display signal 2" is changed several times. TA SpeedControl: 0x5030:6 TA TablePositioning: 0x5030:6 TA ElectronicGearbox: 0x5040:6 and 0x5040:7 TA SyncAndCorrection: 0x5050:6 and 0x5040:7 TA WinderTension: 0x5050:6 TA WinderDancer: 0x5050:6
Which products are affected: Servo inverter i950 with all TAs