i950 TA: Drive decelerates on abort with unexpected braking ramp

What happens?
The function "Abort" leads to an unexpectedly high delay (36000 units/s²). This value cannot be parameterised.
 
When does the behaviour occur?
Activation of the Abort function from the following functions.
TA SpeedControl: ManualJog
TA TablePositioning: ManualJog
TA SyncAndCorrection: ManualJog, Synchronised
TA ElectronicGearbox: ManualJog, Synchronised
TA WinderDancer: ManualJog, Winding
TA WinderTension: ManualJog, Winding
 
Which products are affected? 
i950 BS/ES with TA Speed Control (0x4000:0 = [10])
i950 BS/ES with the TA Table Positioning (0x4000:0 = [20])
i950 BS/ES with TA Sync And Correction (0x4000:0 = [41])
i950 BS/ES with the TA Electronic Gearbox (0x4000:0 = [40])
i950 BS/ES with the TA Winder Dancer (0x4000:0 = [50])
i950 BS/ES with the TA Winder Tension (0x4000:0 = [51])

Short-term measures:
The function of the technology application can be terminated by deactivating the respective active function (SyncOut, HALT or QSP application).
 
Evaluation / recommendations:
The "Abort" function is not useful for these technology applications and should therefore not be used.

Note: No change is planned for this behaviour.