i950 TA SpeedControl / TablePos: Internal Control for Monitoring Signal 2 does not work (corrected from V01.07.04)

Corrected from:
Servo inverter i950 from FW V01.07.04

Response of the new version:
The value entered in 0x5030:117 for Monitoring Signal 2 when Internal Control is activated is transmitted via the bus (fieldbus and onBoardEtherCAT).
 
What happens?
Monitoring signal 2 cannot be simulated for the status signals of the TA (0x5030:101 = 0x01).
The value entered in 0x5030:117 for monitoring signal 2 with activated internal control is not transmitted via the bus (fieldbus and onBoardEtherCAT).

When does the behaviour occur?
When Internal Control is activated for the status signals of the TA (0x5030:101 = 0x01).
 
Which products are affected?
Servo inverter i950 with TA SpeedControl (0x4000 = TA SpeedControl [10])
Servo inverter i950 with TA TablePositioning (0x4000 = TA TablePositioning [20])

Short-term measures:
 -
Evaluation / recommendations:

Automatic Translation