Design Time - Variables: Variable values are not updated during runtime

Corrected from:
EASY UI Designer V01.04

Response of the new version:
As of version V01.04, three groups can be used for communication in the UI Designer.
 
What happens?
The client projects were launched.
The values in the display of a control do not update if the value in the PLC has changed.
However, a value change in the client via the NumericVarIn and TextVarin controls is updated in the PLC.

When does the behaviour occur?
The variables concerned are not in the following folder in the server project:

Project Explorer: Your_Project_Server -> Variables -> Channels -> Groups and here the group "Standard".

Which products are affected?
EASY UI Designer: V01.03.xx.xx

Short-term measures:
Configure all variables in the "Standard" group only.
 
Evaluation / recommendation:
Currently, only the "Standard" group is supported for communication with this version of EASY UI Designer.

URL for linking this AKB article: https://www.lenze.com/en-de/go/akb/202100406/1/