Use of the EPM-S410 under Beckhoff TwinCAT

Corrected from:
-
Response of the new version:
 -

What happens?
The scaling parameterised for channel 1 does not work as described in the documentation. If, for example, the value 0x41 (Siemens S5 format) is set in parameter 0x31xx:001, a different scaling is effective. In this case, 20mA are not scaled to 16384, but to 27648.

Channel two of the EPM-S410 does not show this behaviour.

When does the behaviour occur?
The behaviour occurs when the EPM-S410 is used on the EPM-S131 bus coupler under a Beckhoff controller.
 
Which products are affected?
EPM-S410

Short-term measures:
None

Evaluation / recommendations:
The module can be used. It must be checked during commissioning which scaling is currently active and, if necessary, this must be taken into account during programming.


Automatic Translation