Corrected from:
Servo inverter i950 (from V1.9.1)
Response of the new version:
The speed setpoint is extrapolated until, depending on the sensitivity of the monitoring 0x10F1.2, the QSP becomes active, if this has been configured in 0x605E.
What happens?
The speed setpoint jumps to zero. Only after a delay, depending on the sensitivity of the monitoring 0x10F1.2, does the QSP become active, if this has been configured in 0x605E.
When does the behaviour occur?
When the communication of the system bus is interrupted during operation with conductance transmission.
Which products are affected?
Servo inverter i950 with TA Electronic Gearbox (0x4000:0 = [40])
Servo inverter i950 with TA Sync And Correction (0x4000:0 = [41])
Short-term measures:
-
Evaluation / recommendations:
-