Parameters are not reset to factory settings by device command

Removed from:
-

Behavior of the new version:
-

 
Description of the behavior:
When the device commands 'Load default settings' (0x2022:001) or 'Load TA default settings' (0x2022:039) are executed, not all parameters are reset to their factory settings.

Under what conditions does the behavior occur?
The behavior described above occurs with non-persistent technology application (TA) parameters. They retain their last set value after execution of the above-mentioned device commands. This applies, for example:
  • 0x5030:001 (Internal Control Interface In) and
  • 0x5030:010 (control signals)
Affected products:
Servo Inverter i950

Short-term measures, Recommendations, Rating:
Manually reset the parameters that are not reset to factory settings by the device commands. To do this, you can use the comparison function of the EASY Starter to compare the current parameter set in the i950 with the factory setting.

[Automatic Translation]